Skip to content
OpenAdvisories

Summary

The CmpWebServer component in the CODESYS Control Runtime allows users to create browser-based visualizations for monitoring and controlling industrial processes.
Due to improper bounds checking, a specially crafted HTTP request from an unauthenticated remote attacker may lead to a size-limited out-of-bounds write, causing a denial of service of the affected device.

The CODESYS Control runtime system is only affected if the web server is active, which by default requires a running application with an enabled Web Visualization.

Details

Impact
Successful exploitation allows an unauthenticated remote attacker to trigger an out-of-bounds write, causing the CODESYS Control Runtime to crash and resulting in a denial of service on the affected device.

Remediation
Update the following products to version 3.5.22.20.
* CODESYS Control RTE (SL)
* CODESYS Control RTE (for Beckhoff CX) SL
* CODESYS Control Win (SL)
* CODESYS HMI (SL)
* CODESYS Runtime Toolkit

Update the following products to version 4.21.0.0.
* CODESYS Control for BeagleBone SL
* CODESYS Control for emPC-A/iMX6 SL
* CODESYS Control for IOT2000 SL
* CODESYS Control for Linux ARM SL
* CODESYS Control for Linux SL
* CODESYS Control for PFC100 SL
* CODESYS Control for PFC200 SL
* CODESYS Control for PLCnext SL
* CODESYS Control for Raspberry Pi SL
* CODESYS Control for WAGO Touch Panels 600 SL
* CODESYS Virtual Control SL

The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.