Summary
The monitoring functionality of affected CODESYS Control runtime systems processes read and write requests to PLC application data sent by the CODESYS Development System and other clients such as HMIs.
Due to improper synchronization in the CmpMonitor2 component when processing concurrent requests from multiple clients, incorrect data may be read or written, potentially resulting in unexpected behavior of the affected product.
PLCs based on the CODESYS Runtime Toolkit or CODESYS Safety SIL2 are affected if they allow simultaneous access by two or more clients via the CODESYS protocol. In CODESYS Development System 3, simultaneous access to the included Simulation Runtime can only occur when access by an external client, such as an HMI, has been explicitly enabled through dedicated configuration. The default configuration of CODESYS Development System 3 is not affected.
The vulnerability can be exploited by an authenticated remote attacker with monitoring access by issuing concurrent requests to an affected product.
Details
Impact
Successful exploitation may allow an authenticated remote attacker with monitoring access to cause incorrect data processing, malfunction of the affected products, or a denial-of-service condition.
Remediation
Update the following products to version 3.5.22.40.
* CODESYS Control RTE (SL)
* CODESYS Control RTE (for Beckhoff CX) SL
* CODESYS Control Win (SL)
* CODESYS Runtime Toolkit
* CODESYS Safety SIL2
* CODESYS HMI (SL)
* CODESYS Development System 3
Update the following products to version 4.23.0.0.
* CODESYS Control for BeagleBone SL
* CODESYS Control for emPC-A/iMX6 SL
* CODESYS Control for IOT2000 SL
* CODESYS Control for Linux ARM SL
* CODESYS Control for Linux SL
* CODESYS Control for PFC100 SL
* CODESYS Control for PFC200 SL
* CODESYS Control for PLCnext SL
* CODESYS Control for Raspberry Pi SL
* CODESYS Control for WAGO Touch Panels 600 SL
* CODESYS Virtual Control SL
The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
Vulnerabilities 1
-
High 8.1
Improper Synchronization in Monitoring in CODESYS Control Runtime
Affected products do not properly synchronize access to their monitoring functionality. When multiple clients send concurrent requests, this may lead to incorrect reads or writes, or to corruption of internal memory structures. An authenticated remote attacke…
Revision history
-
#1.1.0
Updated remediation category - fixed SL runtimes are now available, formal adaptions.
-
#1.0.0
Initial revision.
References
-
CERT@VDE Security Advisories for CODESYS GmbH
https://www.certvde.com/en/advisories/vendor/codesys
-
Advisory2026-12_VDE-2026-097: CODESYS Control Runtime - Improper Synchronization in Monitoring - HTML
https://www.certvde.com/en/advisories/VDE-2026-097/
-
CODESYS Security Advisories
https://www.codesys.com/security/security-reports.html
-
Advisory2026-12_VDE-2026-097: CODESYS Control Runtime - Improper Synchronization in Monitoring - PDF
https://api-www.codesys.com/fileadmin/user_upload/CODESYS_Group/Ecosystem/Up-to-Date/Security/Security-Advisories/Advisory2026-12_CDS-94929.pdf