Vulnerabilities 8
-
Critical 9.8CVE-2012-6437 EPSS 11%
Rockwell Automation ControlLogix PLC Improper Authentication
The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitation of this vulnerability could cause los…
-
High 8.5CVE-2012-6439 EPSS 23%
Rockwell Automation ControlLogix PLC Improper Access Control
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that changes the product’s configuration and network parameters, a DoS condition can occur. This…
-
High 7.5CVE-2012-6435 EPSS 43%
Rockwell Automation ControlLogix PLC Improper Access Control
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the CPU to stop logic execution and enter a fault state, a DoS can occur. This si…
-
High 7.5CVE-2012-6436 EPSS 35%
Rockwell Automation ControlLogix PLC Improper Input Validation
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the CPU to crash. Successful ex…
-
High 7.5CVE-2012-6438 EPSS 36%
Rockwell Automation ControlLogix PLC Improper Input Validation
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the NIC to crash. Successful ex…
-
High 7.5CVE-2012-6442 EPSS 35%
Rockwell Automation ControlLogix PLC Improper Access Control
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the product to reset, a DoS can occur. This situation could cause loss of availab…
-
Medium 5.0CVE-2012-6441 EPSS 57%
Rockwell Automation ControlLogix PLC Information Exposure
An information exposure of confidential information results when the device receives a specially crafted CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP. Successful exploitation of this vulnerability could cause loss of confident…
-
Medium 4.8
Rockwell Automation ControlLogix PLC Improper Input Validation
The Web server password authentication mechanism used by the products is vulnerable to a MitM and Replay attack. Successful exploitation of this vulnerability will allow unauthorized access of the product’s Web server to view and alter product configuration a…
Revision history
-
#2
Advisory converted into a CSAF
-
#1
Initial Publication
References
-
ICS Advisory ICSA-13-011-03 - Web Version
https://www.cisa.gov/news-events/ics-advisories/icsa-13-011-03
-
Recommended Practices
https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01
-
Recommended Practices
https://www.cisa.gov/resources-tools/resources/ics-recommended-practices
-
Recommended Practices
https://www.cisa.gov/topics/industrial-control-systems
-
Recommended Practices
https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf
-
Recommended Practices
https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf
-
Recommended Practices
https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B
-
Recommended Practices
https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf
-
Recommended Practices
https://www.cisa.gov/uscert/ncas/tips/ST04-014