Hitachi Energy Gateway Station

Published Mar 6, 2023 · Updated Mar 6, 2023

Summary

Successful exploitation of these vulnerabilities could cause part of GWS fail to start, allow unauthorized actors to run scripts, and/or cause a denial-of-service.

Vulnerabilities 4

  • High 7.5

    A vulnerability exists during the start of the affected SYS600, where an input validation flaw causes a buffer-overflow while reading a specific configuration file. Subsequently SYS600 will fail to start. The configuration file can only be accessed by ...

    Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator acces…

  • High 7.5

    A vulnerability exists in the ICCP stack of the affected SYS600 versions due to validation flaw in the process that establishes the ICCP communication. The validation flaw will cause a denial-of-service when ICCP of SYS600 is request to forward any da ...

    Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too di…

  • High 7.5

    A vulnerability exists in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS ...

    Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability…

  • Medium 5.3

    A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected conne ...

    Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connect…