Summary
Successful exploitation of these vulnerabilities disclose sensitive information, modify device settings, escalate privileges, or cause a denial-of-service condition on the affected device.
Vulnerabilities 7
-
High 8.3
AutomationDirect CLICK PLUS Predictable Seed in Pseudo-Random Number Generator
A predictable seed in pseudo-random number generator vulnerability has been discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software implements a predictable seed for its pseudo-random number generator,…
-
High 8.3
AutomationDirect CLICK PLUS Use of a Broken or Risky Cryptographic Algorithm
The use of a broken or risky cryptographic algorithm was discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software uses an insecure implementation of the RSA encryption algorithm.
-
Medium 6.8
AutomationDirect CLICK PLUS Missing Authorization
An authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulner…
-
Medium 5.9
AutomationDirect CLICK PLUS Improper Resource Shutdown or Release
An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all availabl…
-
Medium 5.9
AutomationDirect CLICK PLUS Improper Resource Shutdown or Release
An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all availabl…
-
Medium 5.3
AutomationDirect CLICK PLUS Use of Hard-coded Cryptographic Key
The use of a hard-coded cryptographic key was discovered in firmware version 3.60 of the Click Plus PLC. The vulnerability relies on the fact that the software contains a hard-coded AES key used to protect the initial messages of a new KOPS session.
-
Medium 4.2
AutomationDirect CLICK PLUS Cleartext Storage of Sensitive Information
Cleartext storage of sensitive information was discovered in Click Programming Software version v3.60. The vulnerability can be exploited by a local user with access to the file system, while an administrator session is active, to steal credentials stored in …
Revision history
-
#1
Initial Publication
References
-
ICSA Advisory ICSA-25-266-01 - Web Version
https://www.cisa.gov/news-events/ics-advisories/icsa-25-266-01
-
Recommended Practices
https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01
-
Recommended Practices
https://www.cisa.gov/resources-tools/resources/ics-recommended-practices
-
Recommended Practices
https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf
-
Recommended Practices
https://www.cisa.gov/topics/industrial-control-systems
-
Recommended Practices
https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf
-
Recommended Practices
https://www.cisa.gov/uscert/ncas/tips/ST04-014
-
Recommended Practices
https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01
-
Recommended Practices
https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf
-
Recommended Practices
https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b
-
Recommended Practices
https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing
-
Recommended Practices
https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks