Summary
Several versions of the SICK Flexi Soft Gateways FX0-GENT, FX0-GMOD, FX0-GPNT and SICK Flexi Classic Gateway UE410 provide a Telnet interface for debugging, which is enabled by factory default. No password is set in the default configuration.
If the password is not set by the customer, a remote unauthorized adversary could connect via Telnet. The adversary may use the debugging interface to subsequently gain access to the boot loader and in the worst case modify the firmware of the devices.
Gateways with a serial number >2311xxxx have the Telnet interface disabled by factory default.
Vulnerabilities 1
-
Critical 9.8
The Flexi Classic and Flexi Soft Gateways SICK UE410-EN3 FLEXI ETHERNET GATEW. with serial number <=2311xxxx all Firmwa…
Revision history
-
#2
Updated Advisory: URL for SICK Operating Guidelines has been updated
-
#1
Initial Release
References
-
SICK PSIRT Security Advisories
https://sick.com/psirt
-
SICK Operating Guidelines
https://www.sick.com/media/docs/9/19/719/special_information_sick_operating_guidelines_cybersecurity_by_sick_en_im0106719.pdf
-
ICS-CERT recommended practices on Industrial Security
http://ics-cert.us-cert.gov/content/recommended-practices
-
CVSS v3.1 Calculator
https://www.first.org/cvss/calculator/3.1