Skip to content
OpenAdvisories
Critical SEVD-2021-194-01 6 CVEs

EcoStruxureTM Control Expert, EcoStruxureTM Process Expert, SCADAPack RemoteConnect™ x70, and Modicon Controllers M580 and M340

Published Jul 13, 2021 · Updated Aug 13, 2024 · Revision 10

Summary

Schneider Electric is aware of multiple vulnerabilities in its EcoStruxure™ Control Expert , EcoStruxure™ Process Expert, SCADAPack RemoteConnect™ x70, and Modicon M580 and M340 control products. These vulnerabilities pose several risks, primary among these is the possibility of arbitrary code execution and loss of confidentiality and integrity of the project file.
With all products affected an attack would first involve an authenticated user gaining access to the engineering station; or an unauthenticated user gaining access to a project file or to the process control network.
Our findings demonstrate that while the discovered vulnerabilities affect Schneider Electric offers, it is possible to mitigate the potential impacts by following standard guidance, specific instructions; and in some cases, the fixes provided by Schneider Electric to remove the vulnerabilities.
Please ensure that if you are an EcoStruxure™ Control Expert user to apply the latest security updates provided below. For users of any of the mentioned products see the mitigation section in this security notice for further information on how to help protect your system from possible attack.
Schneider Electric encourages all industrial companies to ensure they have implemented cybersecurity best practices across their operations and supply chains to reduce cyber risks. Where appropriate this includes locating industrial systems and remotely accessible devices behind firewalls; installing physical controls to prevent unauthorized access; preventing mission-critical systems and devices from being accessed from outside networks; systematically applying security patches.
March 2023 Update: Remediation for the Modicon M580 CPU is available for download (page 8).
We will update this document when the fixes are available. To ensure you are informed of the upcoming security notifications updates, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/security-notifications.jsp
Note: A Proof-of-Concept script code that could potentially exploit some of these vulnerabilities has been discovered. Remediation and mitigation actions documented in this notification document will reduce the risk of exploit.

Vulnerabilities 6

  • High 7.3

    WAGO/M&M Software Deserialization of untrusted data in fdtCONTAINER component

    M&M Software fdtCONTAINER Component in versions below 3.5.20304.x and between 3.6 and 3.6.20304.x is vulnerable to deserialization of untrusted data in its project storage.

  • Medium 6.5

    Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, …

  • Unscored —

    Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP…

  • Unscored —

    Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP…

  • Unscored —

    Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP…

  • Unscored —

    Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP…

Revision history

  1. #9.0.0

    A remediation is available for the Modicon M580 CPU Safety (page 9)

  2. #8.0.0

    Remediation for the Modicon M580 CPU is available for download

  3. #7.0.0

    The Modicon M580 SV4.02 firmware has been retracted for quality issues and is no longer available for download. Additional mitigations have been introduced for Modicon M580 CPU and M580 CPU Safety, and we urge customers to deploy these mitigations to further reduce the risk of potential exploitation of identified vulnerabilities

  4. #6.0.0

    A clarification was added to the list of affected products by splitting Modicon M580 and Modicon M580 Safety CPU ranges. The purpose of the notification update is to inform customers that the latest fix Modicon M580 V4.02 does not apply to the Safety range of M580. It is highly recommended that customers using Modicon M580 Safety ranges continue to implement the mitigations shared in this document

  5. #5.1.0

    The version number for Modicon M580 that addresses these vulnerabilities has been updated from V4.01 to V4.02.

  6. #5.0.0

    A fix is available for Modicon M580 V4.01 that addresses the vulnerabilities related to these issues. Note that a complete remediation is a two-step process and will require an upgrade of the engineering software: EcoStruxure™ Control Expert, EcoStruxure™ Process Expert or SCADAPack RemoteConnect™, in addition to an upgrade of the Modicon controller firmware: M340 and M580. EcoStruxure™ Control Expert version 15.1 and EcoStruxure™ Process Expert V2021 include a fix for the vulnerabilities reported in this document and have been removed from the affected products list.

  7. #4.0.0

    A release is available for SCADAPack RemoteConnect™ R2.7.3 that addresses workstation vulnerabilities related to the issues listed. (page 6) It has been determined that SCADAPack RemoteConnect™ versions prior to R2.7.3 are not affected by CVE-2021-22779, CVE-2021-22781, CVE-2021-22782.

  8. #3.0.0

    A release is available for Modicon M340 controllers that addresses CVE-2021-22779, in conjunction with the latest release of EcoStruxure™ Control Expert. Subsequent firmware releases are planned to address the Modicon M580 PLC’s to complete the remediations that will fix CVE-2021-22779.

  9. #2.0.0

    A release is available for EcoStruxure™ Control Expert v15.1 and EcoStruxure™ Process Expert 2021 that addresses workstation vulnerabilities related to the issues listed below. A subsequent release is planned to address the Modicon M580 and Modicon M340 PLC’s to complete the remediations.

  10. #1.0.0

    Original Release

References