Skip to content
OpenAdvisories
Critical SSA-625850 3 CVEs

SSA-625850: Multiple WIBU Systems CodeMeter Vulnerabilities Affecting the Desigo CC Product Family and SENTRON powermanager

Published Nov 14, 2023 · Updated Aug 13, 2024 · Revision 2

Summary

Versions V5.0 through V7 of the Desigo CC product family (Desigo CC, Desigo CC Compact, Desigo CC Connect, Cerberus DMS), as well as the Desigo CC-based SENTRON powermanager, are affected by multiple vulnerabilities in the underlying third-party component WIBU Systems CodeMeter Runtime.
Successful exploitation of these vulnerabilities could allow remote attackers to execute arbitrary code on the Desigo CC server, or create a denial of service condition.
While all Desigo CC version lines V5.0, V5.1 and V6 are affected by all listed vulnerabilities, V7 is only affected by CVE-2023-3935.

Siemens has released a patch to update the CodeMeter Runtime component and recommends to apply the patch on affected systems.

Vulnerabilities 3

  • Critical 9.8

    Wibu: Buffer Overflow in CodeMeter Runtime

    A heap buffer overflow vulnerability in Wibu CodeMeter Runtime network service up to version 7.60b allows an unauthenticated, remote attacker to achieve RCE and gain full access of the host system.

  • Unscored —
    CVE-2021-20093 EPSS 33%

    A buffer over-read vulnerability exists in Wibu-Systems CodeMeter versions < 7.21a. An unauthenticated remote attacker …

  • Unscored —

    A denial of service vulnerability exists in Wibu-Systems CodeMeter versions < 7.21a. An unauthenticated remote attacker…

Revision history

  1. #2

    Added SENTRON powermanager

  2. #1

    Publication Date

References