Summary
The reported vulnerability allows an attacker who has network access to the device to execute code with specially crafted packets.
Details
Impact
By exploiting the described vulnerabilities the attacker potentially is able to manipulate or disrupt the device.
Mitigation
* Disable I/O-Check service
* Restrict network access to the device.
* Do not directly connect the device to the internet.
Remediation
The I/O-Check service protocol is only needed during installation and commissioning, not during normal operations. It is highly recommended to disable the I/O-Check service after commissioning. This is the easiest and securest way to protect your device from the listed vulnerabilities.
Regardless to the action described above, the vulnerability has been fixed in FW11, released in December 2017.
Vulnerabilities 1
-
Critical 10.0
Command Injection Vulnerability in I/O-Check Service of WAGO PFC100, PFC200 and Touch Panel 600 Series with firmware versions <=FW10
The reported vulnerability allows an attacker who has network access to the device to execute code with specially crafted packets in WAGO Series PFC 100 (750-81xx/xxx-xxx), Series PFC 200 (750-82xx/xxx-xxx), Series Wago Touch Panel 600 Standard Line (762-4xxx…