High VDE-2022-024 1 CVE

Auma: SIMA² Master Station Denial of Service Vulnerability on Automation Runtime Webserver

Published Jun 15, 2022 · Updated May 14, 2025 · Revision 2

Summary

Improper buffer restrictions in the webserver used in SIMA² Master Station software versions < V 2.6 may allow an unauthenticated network-based attacker to stop the cyclic program on the device and cause a denial of service.

Details

Impact
The webserver component of the automation runtime used implements insufficient checks on handling file uploads. This implementation could result in a memory violation, which in turn affects the stability of automation runtime.
An attacker could leverage this vulnerability to potentially cause a denial of service of the device.

Mitigation
AUMA recommends the following specific workarounds and mitigations: The access to the SIMA² should be restricted to legitimate network partners, using e.g. a sufficient firewall setup and robust network segmentation. In general, AUMA recommends implementing the Product Security Guideline for uses on Cybersecurity for the SIMA² Master Station.

Remediation
The described vulnerabilities have been fixed in the product versions with software version V 2.6 or higher. SIMA² Master Stations with software versions < V 2.6 can be upgraded. AUMA recommends applying a product update at the earliest convenience

Vulnerabilities 1

  • High 8.6

    Denial of service vulnerability on Automation Runtime webserver

    Buffer Overflow vulnerability in B&R Automation Runtime webserver allows an unauthenticated network-based attacker to stop the cyclic program on the device and cause a denial of service.