Summary
Improper buffer restrictions in the webserver used in SIMA² Master Station software versions < V 2.6 may allow an unauthenticated network-based attacker to stop the cyclic program on the device and cause a denial of service.
Details
Impact
The webserver component of the automation runtime used implements insufficient checks on handling file uploads. This implementation could result in a memory violation, which in turn affects the stability of automation runtime.
An attacker could leverage this vulnerability to potentially cause a denial of service of the device.
Mitigation
AUMA recommends the following specific workarounds and mitigations: The access to the SIMA² should be restricted to legitimate network partners, using e.g. a sufficient firewall setup and robust network segmentation. In general, AUMA recommends implementing the Product Security Guideline for uses on Cybersecurity for the SIMA² Master Station.
Remediation
The described vulnerabilities have been fixed in the product versions with software version V 2.6 or higher. SIMA² Master Stations with software versions < V 2.6 can be upgraded. AUMA recommends applying a product update at the earliest convenience
Vulnerabilities 1
-
High 8.6
Denial of service vulnerability on Automation Runtime webserver
Buffer Overflow vulnerability in B&R Automation Runtime webserver allows an unauthenticated network-based attacker to stop the cyclic program on the device and cause a denial of service.
Revision history
-
#2
Fix: added distribution
-
#1
initial revision
References
-
VDE-2022-024: Auma: SIMA² Master Station Denial of Service Vulnerability on Automation Runtime Webserver - HTML
https://certvde.com/de/advisories/VDE-2022-024/
-
CERT@VDE Security Advisories for AUMA Riester GmbH & Co. KG
https://certvde.com/en/advisories/vendor/auma/