Summary
The 'legal information' plugin of web-based-management contained a vulnerability which allowed execution of arbitrary commands with privileges of www user.
UPDATE A 15.06.2023 :
Removed PFC100 with FW23 as affected product and from solution
PFC200 with FW23 is only affected on 750-821x/xxx-xxx
Renamed "FW22 Patch 1" to "FW22 SP1" to match the versions of the download portal
Details
Impact
Exploiting the vulnerability provides arbitrary command execution with privileges of the 'www' user. Via this flaw an attacker can change device configuration, create users or even take over the system.
Mitigation
As general security measures strongly WAGO recommends:
Use general security best practices to protect systems from local and network attacks.
Do not allow direct access to the device from untrusted networks.
Update to the latest firmware according to the table in chapter solutions.
Industrial control systems (ICS) should not be directly accessible from the Internet, but should be protected by consistently applying the defense-in-depth strategy.
The BSI provides general information on securing ICS in the ICS Compendium (https://www.bsi.bund.de/SharedDocs/Downloads/EN/BSI/ICS/ICS-Security_compendium.pdf).
Remediation
Wago recommends all affected users to update to the firmware version listed below:
| Article No° | Product Name | Fixed Version |
|----------------------|------------------------------|----------------------------------|
| 751-9301 | Compact Controller CC100 | FW24 |
| 752-8303/8000-002 | Edge Controller | FW22 |
| 752-8303/8000-002 | Edge Controller | FW24 |
| 750-81xx/xxx-xxx | PFC100 | FW22 SP1 |
| 750-82xx/xxx-xxx | PFC200 | FW22 SP1 l |
| 750-821x/xxx-xxx | PFC200 | FW24 |
| 762-5xxx | Touch Panel 600 Advanced Line| FW22 SP1 |
| 762-5xxx | Touch Panel 600 Advanced Line| FW24 |
| 762-6xxx | Touch Panel 600 Marine Line | FW22 SP1 |
| 762-6xxx | Touch Panel 600 Marine Line | FW24 |
| 762-4xxx | Touch Panel 600 Standard Line| FW22 SP1 |
| 762-4xxx | Touch Panel 600 Standard Line| FW24 |
Vulnerabilities 1
-
Critical 9.8
WAGO: WBM Command Injection in multiple products
In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise.
Revision history
-
#2
Fix: quotation mark
-
#1
Initial revision.
References
-
VDE-2023-007: WAGO: Unauthenticated command execution via Web-based-management UPDATE A - HTML
https://certvde.com/en/advisories/VDE-2023-007/
-
WAGO PSIRT
https://www.wago.com/psirt
-
CERT@VDE Security Advisories for WAGO GmbH & Co. KG
https://certvde.com/en/advisories/vendor/wago/