Summary

Several WAGO Firmwares are vulnerable to an incorrect calculation of the buffer size in the CODESYS OPC UA STACK. This can lead to a crash of the runtime of the affected firmware versions installed on several devices.

Details

Impact
The OPC UA Stack is used by both the CODESYS OPC UA Server and Client for data exchange with OPC UA clients like SCADA or HMIs, and OPC UA servers like PLCs. A vulnerability exists where a specially crafted request can cause the system to miscalculate the buffer size, leading to a crash during buffer initialization. Attackers can exploit this flaw by sending malicious requests to crash the CODESYS runtime system. The CODESYS Control runtime system includes both the OPC UA client and server, while the CODESYS HMI includes only the OPC UA client.

Remediation
Update to Firmware version 22 Patch 2, Firmware version 27 or Firmware version 4 for the basic controller. For the latest custom firmware, please contact the WAGO support.

Mitigation
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg

Vulnerabilities 1

Revision history

  1. #3

    Fix: firmware category

  2. #2

    fixed version

  3. #1

    Initial release