Beckhoff: Deserialization of untrusted data by TwinCAT 3 Engineering

Published Sep 9, 2025 · Updated Sep 9, 2025

Summary

Beckhoff's TwinCAT 3 Engineering software is intented to craft automation projects consisting of a set of files which are stored locally as files underneath an individual folder or in a packed file. The TwinCAT 3 Engineering stores user settings and preferences among the non packed local files which are relevant to continue former work on the project conventienly. TwinCAT 3 Engineering stores such settings in files which are called "Solution User Options (.suo) File". When such settings are manipulated or crafted by an adversary in a specific way then TwinCAT 3 Engineering executes arbitrary commands as determined by these settings when the user uses TwinCAT 3 Engineering to open the project. These arbitrary commands are executed in the user context.

Please note that solution user option files should not be checked in to source code control. This is also a best practice when working with source code projects and solutions. For example, see https://learn.microsoft.com/en-us/visualstudio/extensibility/internals/solution-user-options-dot-suo-file and https://infosys.beckhoff.com/content/1033/tc3_sourcecontrol/14604066827.html.

The vulnerability is similar to older vulnerabilities that were addressed in the CODESYS Development System V3 product from CODESYS GmbH with CVE-2021-21864, CVE-2021-21865, CVE-2021-21866, CVE-2021-21867, CVE-2021-21868, CVE-2021-21869, and the associated Advisory 2021-13 from CODESYS GmbH.

Details

Impact
An attacker with access to local files can trick a local user into executing arbitrary commands by opening a deliberately manipulated project file with an affected engineering tool. These arbitrary commands are executed in the user context. When older affected versions of the engineering tool are installed then the deliberate manipulation of the project file can cause that these are used to open it.

Please note that TwinCAT 3 Engineering offers the "Remote Manager" feature (see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/index.html?id=1584127271344589360) which means that older versions of TwinCAT 3 Engineering can stay installed in parallel to more recent versions. TwinCAT projects can be "pinned" to be edited with a fixed version, see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/3154642571.html. If such a pinned project is opened while a more recent version of TwinCAT 3 Engineering is installed and at the same time the matching older version of TwinCAT 3 Engineering is still installed then the project is automatically passed from the more recent version to the matching older version and edited with that older version where that older version is vulnerable.

General Recommendation
Developers shall care for opening projects from trusted sources only. This is a best practice when working with source code and the main content of a project which is crafted with TwinCAT 3 Engineering is source code which is to be compiled to activate it on a target.

Solution user option files should not be checked in to source code control. This is also a best practice when working with source code projects and solutions. For example, see https://learn.microsoft.com/en-us/visualstudio/extensibility/internals/solution-user-options-dot-suo-file and https://infosys.beckhoff.com/content/1033/tc3_sourcecontrol/14604066827.html.

Avoid pinning of projects to exact versions of TwinCAT 3 Engineering, see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/index.html?id=1584127271344589360 and https://infosys.beckhoff.com/content/1033/tc3_remote_manager/3154642571.html. Always open projects with the most recent version of TwinCAT 3.

Remediation
Please update to a recent version of the affected product and uninstall older versions of TwinCAT 3 Engineering. Make sure that older versions of TwinCAT 3 Engineering do not occur as "Remote Manager" versions, see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/index.html?id=1584127271344589360. Remove the "pinning" from your projects to older versions of TwinCAT 3 Engineering, if present, see https://infosys.beckhoff.com/content/1033/tc3_remote_manager/3154642571.html.