High VDE-2025-092 3 CVEs

Beckhoff: Privilege escalation and information leak via Beckhoff Device Manager

Published Jan 27, 2026 · Updated Jan 27, 2026 · Revision 2

Summary

The vulnerability CVE-2025-41726 (NN-2025-0074) allows an authenticated remote user to execute arbitrary commands on the device. This can be exploited over the web UI or via API. In one case the execution of the arbitrary command happens within a privileged process.

The vulnerability CVE-2025-41727 (NN-2025-0075) allows a local user with low privileges on the device to bypass the authentication mechanism of the UI and send commands to a privileged process which it executes on behalf of that user but with higher privileges. This way the local user can escalate privileges.

The vulnerability CVE-2025-41728 (NN-2025-0076) allows an authenticated remote user to cause an out-of-bounds read operation within a specific service process which runs on the device. The read operation might copy sensitive information from the memory of the specific service into a response message which is then provided to the user but the user cannot choose which information is disclosed.

Details

Impact
CVE-2025-41726: On a Beckhoff IPC or CX device an authenticated user can execute arbitrary code by sending specially crafted calls to the web service of the Beckhoff Device Manager or locally via an API and can cause integer overflows which then can lead to arbitrary code execution within privileged processes.

CVE-2025-41727: On a Beckhoff IPC or CX device a local user can bypass the authentication of the Beckhoff Device Manager user interface, allowing them to perform privileged operations and gain administrator access.

CVE-2025-41728: On a Beckhoff IPC or CX device, an authenticated user may be able to disclose confidential information from the memory of a privileged process by sending specially crafted calls to the Beckhoff Device Manager web service that cause an out-of-bounds read operation and thereby potentially copy confidential information into a response.

General Recommendation
Beckhoff IPC and CX devices are intended for industrial use within operational technology (OT). For the Beckhoff Device Manager user interface network access is to be restricted to trustworthy personal. Additionally, it is advisable to restrict local access to trustworthy personal.

When not needed, the Beckhoff Device Manager user interface can be disabled for remote access or even be uninstalled. In example, for disabling remote access the OS firewall can be used to forbid the access to the network port or the web server process can be stopped permanently.

Remediation
Please update to a recent version of the affected components (see below) or update the complete operating system image. Operating system images are available on request from Beckhoff's service (service@beckhoff.com). The setup / installer for Windows 10 and 11 are available on request from Beckhoff's service also.

| Product | Fixed Version |
|----------------------------------|---------------|
| Beckhoff.Device.Manager.XAR tcpkg package | 2.5.3 |
| Beckhoff IPC Diagnostics software for Windows | 2.5.3 |
| MDP.dll library library for Windows CE 6.0 and Embedded Compact 7 on x86 | 1.7.0.0 |
| MDP software package for TwinCAT/BSD | 1.7.0.0 |
| mdp-bhf software package Beckhoff RT Linux(R) | 0.0.5-1 |
| MDP.dll library library for Windows CE 6.0 and Embedded Compact 7 on ARM32 | 1.7.0.0 |