Summary
Several Murrelektronik devices using Profinet are shipped with the default SNMP community names ('public' for read access and 'private' for write access). If these community strings remain unchanged in the field, an unauthenticated attacker with network access to the device can read its configuration and, depending on the writable OIDs, modify device settings.
Details
Impact
An unauthenticated attacker with network access to an affected device can read sensitive configuration data via SNMP read access (loss of confidentiality). With write access to the 'private' community, the attacker can modify device parameters exposed via writable OIDs, which may disrupt device operation or alter the behaviour of connected industrial processes (loss of integrity and potential loss of availability).
General Recommendation
* Configure the device or upstream network equipment (firewall, managed switch) to only accept SNMP queries from explicitly authorized management stations. Use ACLs to block all other sources from reaching UDP port 161 of the device.
* Place affected devices in a dedicated OT or management VLAN that is isolated from general office, guest, and untrusted networks. Block UDP/161 at the network perimeter and between zones to prevent lateral SNMP queries.
* Enable network monitoring, logging, or IDS/IPS rules to detect unauthorized or anomalous SNMP queries directed at the affected devices. Investigate any SNMP write attempts ('private' community usage) as potential indicators of compromise.
* Ensure device management interfaces are not exposed to the internet or to other untrusted networks. Apply defense-in-depth principles by combining physical access control to the OT environment with network-level access restrictions.
Remediation
No vendor fix is currently available for the majority of affected products.
A firmware update addressing vulnerability is planned for early 2027 for the Impact67 Pro (article numbers 54620, 54630) and MVK Pro (article numbers 54600, 54610) product variants.
Vulnerabilities 1
-
Medium 5.9
An SNMP community name is the default (e.g. public), null, or missing.
Revision history
-
#1.0.0
initial release
References
-
Murrelektronik Product Security Incident Response (PSIRT) Team
https://my.murrelektronik.com/home/de/services-support/support/PSIRT
-
CERT@VDE Security Advisories for Murrelektronik
https://certvde.com/en/advisories/vendor/murrelektronik
-
VDE-2026-062: Several Murrelektronik Devices use Default SNMP Community Names - HTML
https://certvde.com/en/advisories/vde-2026-062/