Summary
A remote unauthenticated attacker can exploit a SQL injection vulnerability in PROCON-WEB SCADA to execute arbitrary commands.
Details
Impact
Successful exploitation allows an unauthenticated attacker to read, modify or delete data and to execute arbitrary SQL commands, potentially leading to further compromise of the underlying system.
Remediation
It is strongly advised to update PROCON-WEB SCADA to version 6.11.3.
| Product | Affected Version | Fixed Version |
|---------|-----------------|----------------|
| PROCON-WEB SCADA | <=6.11.2 | 6.11.3 |
Vulnerabilities 1
-
Critical 9.8
SQL injection via unauthenticated GetGridData endpoint
In PROCON-WEB SCADA the endpoint 'GetGridData' is not properly sanitized. This allows a remote unauthenticated attacker to execute arbitrary SQL commands.
Revision history
-
#1.0.0
Initial version
References
-
Weidmueller Security Advisory Board
https://support.weidmueller.com/support-center/popular-resources/security-advisory-board
-
CERT@VDE Security Advisories for Weidmueller
https://certvde.com/de/advisories/vendor/weidmueller/
-
VDE-2026-085: Weidmueller: SQL Injection Vulnerability in PROCON-WEB SCADA - HTML
https://certvde.com/de/advisories/VDE-2026-085