Skip to content
OpenAdvisories
Critical · 9.3 CVE-2014-0769 EUVD-2014-0800GHSA-q52x-cg29-xrxr

Festo CECX-X-(C1/M1) Controller Improper Authentication

Published Apr 25, 2014 · Updated Jul 2, 2025 · Assigned by icscert

Description

The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion do not require authentication for connections to certain TCP ports, which allows remote attackers to (1) modify the configuration via a request to the debug service on port 4000 or (2) delete log entries via a request to the log service on port 4001.

Affected products

VendorProductAffectedFixed
Festo CECX-X-C1 Modular Master Controller with CoDeSys all —
Festo CECX-X-M1 Modular Controller with CoDeSys and SoftMotion all —