Description
Phoenix Contact Classic Line Controllers ILC1x0 and ILC1x1 in all versions/variants are affected by a Denial-of-Service vulnerability. The communication protocols and device access do not feature authentication measures. Remote attackers can use specially crafted IP packets to cause a denial of service on the PLC's network communication module. A successful attack stops all network communication. To restore the network connectivity the device needs to be restarted. The automation task is not affected.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Phoenix Contact | ILC1x | ILC1x0 all variants, ILC1x1 all variants | — |
Advisories 1
- VDE-2021-019 PHOENIX CONTACT: Security Advisory for ILC1x1 Industrial controllers CERT@VDE · May 14, 2025