High · 7.5 CVE-2021-35533 EUVD-2021-22169GHSA-wv2v-prmm-j684

Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series

Published Nov 26, 2021 · Updated Sep 16, 2024 · Assigned by Hitachi Energy

Description

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Affected products

VendorProductAffectedFixed
Hitachi Energy RTU500 series CMU Firmware version 12.0 – ≤ 12.0.*, CMU Firmware version 12.2 – ≤ 12.2.*, CMU Firmware version 12.4 – ≤ 12.4.* —