Description
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Hitachi Energy | RTU500 series | CMU Firmware version 12.0 – ≤ 12.0.*, CMU Firmware version 12.2 – ≤ 12.2.*, CMU Firmware version 12.4 – ≤ 12.4.* | — |
Advisories 1
- ICSA-21-336-04 Hitachi Energy RTU500 series BCI CISA ICS & IT advisories · Dec 2, 2021