Skip to content
OpenAdvisories
Unscored CVE-2021-41545 EUVD-2021-28563GHSA-hw79-77g6-22xq

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo P…

Published May 10, 2022 · Updated Aug 4, 2024 · Assigned by siemens

Description

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.

Affected products

VendorProductAffectedFixed
Siemens Desigo DXR2 All versions < V01.21.142.5-22 —
Siemens Desigo PXC3 All versions < V01.21.142.4-18 —
Siemens Desigo PXC4 All versions < V02.20.142.10-10884 —
Siemens Desigo PXC5 All versions < V02.20.142.10-10884 —

Advisories 2

References