Critical · 9.8 CVE-2022-2336 EUVD-2022-34605GHSA-rvxf-x8j2-f3x9

Softing Secure Integration Server Improper Authentication

Published Aug 17, 2022 · Updated Apr 16, 2025 · Assigned by icscert

Description

Softing Secure Integration Server, edgeConnector, and edgeAggregator software ships with the default administrator credentials as `admin` and password as `admin`. This allows Softing to log in to the server directly to perform administrative functions. Upon installation or upon first login, the application does not ask the user to change the `admin` password. There is no warning or prompt to ask the user to change the default password, and to change the password, many steps are required.

Affected products

VendorProductAffectedFixed
Softing Secure Integration Server V1.22 —
Softing edgeConnector Siemens V3.10 —
Softing edgeConnector 840D V3.10 —
Softing edgeConnector Modbus V3.10 —
Softing edgeAggregator V3.10 —