Description
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The application, after a successful login, sets the session cookie on the browser via client-side JavaScript code, without applying any security attributes (such as “Secure”, “HttpOnly”, or “SameSite”). Any attempts to browse the application via unencrypted HTTP protocol would lead to the transmission of all his/her session cookies in plaintext through the network. An attacker could then be able to sniff the network and capture sensitive information.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Siemens | Desigo DXR2 | All versions < V01.21.142.5-22 | — |
| Siemens | Desigo PXC3 | All versions < V01.21.142.4-18 | — |
| Siemens | Desigo PXC4 | All versions < V02.20.142.10-10884 | — |
| Siemens | Desigo PXC5 | All versions < V02.20.142.10-10884 | — |
Advisories 2
- ICSA-22-132-10 Siemens Desigo PXC and DXR Devices CISA ICS & IT advisories · Jun 16, 2022
- SSA-626968 SSA-626968: Multiple Webserver Vulnerabilities in Desigo PXC and DXR Devices Siemens ProductCERT · Jun 14, 2022