Skip to content
OpenAdvisories
High · 7.5 CVE-2022-2502 EUVD-2022-34760GHSA-45rh-q5fv-wf42

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can…

Published Jul 26, 2023 · Updated Mar 5, 2025 · Assigned by Hitachi Energy

Description

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

Affected products

VendorProductAffectedFixed
Hitachi Energy RTU500 series RTU500 series CMU Firmware version 13.3.1, RTU500 series CMU Firmware version 13.3.2 RTU500 series CMU Firmware version 13.3.3

Advisories 2

References