Skip to content
OpenAdvisories
High · 7.5 CVE-2022-28613 EUVD-2022-33055GHSA-9m5v-m5wp-xcm2

Specially Crafted Modbus TCP Packet Vulnerability in RTU500 series

Published May 2, 2022 · Updated Sep 25, 2024 · Assigned by Hitachi Energy

Description

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

Affected products

VendorProductAffectedFixed
Hitachi Energy RTU500 series CMU Firmware 12.0.*, 12.2.*, 12.4.*, 12.6.*, 12.7.*, 13.2.* —

Advisories 1

References