Skip to content
OpenAdvisories

Description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), Desigo PXC00-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC00-U (All versions >= V2.3 < V6.30.37), Desigo PXC001-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC100-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC12-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC128-U (All versions >= V2.3 < V6.30.37), Desigo PXC200-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC22.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC36.1-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC50-E.D (All versions >= V2.3 < V6.30.37), Desigo PXC64-U (All versions >= V2.3 < V6.30.37), Desigo PXM20-E (All versions >= V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.

Affected products

VendorProductAffectedFixed
Siemens APOGEE MBC (PPC) (BACnet) All versions —
Siemens APOGEE MBC (PPC) (P2 Ethernet) All versions —
Siemens APOGEE MEC (PPC) (BACnet) All versions —
Siemens APOGEE MEC (PPC) (P2 Ethernet) All versions —
Siemens APOGEE PXC Compact (BACnet) < V3.5.7 V3.5.7
Siemens APOGEE PXC Compact (P2 Ethernet) < V2.8.21 V2.8.21
Siemens APOGEE PXC Modular (BACnet) < V3.5.7 V3.5.7
Siemens APOGEE PXC Modular (P2 Ethernet) < V2.8.21 V2.8.21
Siemens Desigo PXC00-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC00-U V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC001-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC100-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC12-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC128-U V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC200-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC22-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC22.1-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC36.1-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC50-E.D V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXC64-U V2.3 – < V6.30.37 V6.30.37
Siemens Desigo PXM20-E V2.3 – < V6.30.37 V6.30.37
Siemens Nucleus NET for Nucleus PLUS V1 All versions < V5.2a —
Siemens Nucleus NET for Nucleus PLUS V2 All versions < V5.4 —
Siemens Nucleus ReadyStart V3 V2012 All versions < V2012.08.1 —
Siemens Nucleus ReadyStart V3 V2017 All versions < V2017.02.4 —
Siemens Nucleus Source Code — —
Siemens TALON TC Compact (BACnet) < V3.5.7 V3.5.7
Siemens TALON TC Modular (BACnet) < V3.5.7 V3.5.7

Advisories 5