Description
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). Endpoints of the “Operation” web application that interpret and execute Axon language queries allow file read access to the device file system with root privileges. By supplying specific I/O related Axon queries, a remote low-privileged attacker can read sensitive files on the device.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Siemens | Desigo PXM30-1 | All versions < V02.20.126.11-41 | — |
| Siemens | Desigo PXM30.E | All versions < V02.20.126.11-41 | — |
| Siemens | Desigo PXM40-1 | All versions < V02.20.126.11-41 | — |
| Siemens | Desigo PXM40.E | All versions < V02.20.126.11-41 | — |
| Siemens | Desigo PXM50-1 | All versions < V02.20.126.11-41 | — |
| Siemens | Desigo PXM50.E | All versions < V02.20.126.11-41 | — |
| Siemens | PXG3.W100-1 | All versions < V02.20.126.11-37 | — |
| Siemens | PXG3.W100-2 | All versions < V02.20.126.11-41 | — |
| Siemens | PXG3.W200-1 | All versions < V02.20.126.11-37 | — |
| Siemens | PXG3.W200-2 | All versions < V02.20.126.11-41 | — |
Advisories 2
- ICSA-22-286-06 Siemens Desigo PXM Devices CISA ICS & IT advisories · Oct 11, 2022
- SSA-360783 SSA-360783: Multiple Webserver Vulnerabilities in Desigo PXM Devices Siemens ProductCERT · Oct 11, 2022