Description
A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V9.50), SIPROTEC 5 6MD85 (CP200) (All versions), SIPROTEC 5 6MD85 (CP300) (All versions < V9.50), SIPROTEC 5 6MD86 (CP200) (All versions), SIPROTEC 5 6MD86 (CP300) (All versions < V9.50), SIPROTEC 5 6MD89 (CP300) (All versions < V9.64), SIPROTEC 5 6MU85 (CP300) (All versions < V9.50), SIPROTEC 5 7KE85 (CP200) (All versions), SIPROTEC 5 7KE85 (CP300) (All versions < V9.64), SIPROTEC 5 7SA82 (CP100) (All versions < V8.90), SIPROTEC 5 7SA82 (CP150) (All versions < V9.50), SIPROTEC 5 7SA84 (CP200) (All versions), SIPROTEC 5 7SA86 (CP200) (All versions), SIPROTEC 5 7SA86 (CP300) (All versions < V9.50), SIPROTEC 5 7SA87 (CP200) (All versions), SIPROTEC 5 7SA87 (CP300) (All versions < V9.50), SIPROTEC 5 7SD82 (CP100) (All versions < V8.90), SIPROTEC 5 7SD82 (CP150) (All versions < V9.50), SIPROTEC 5 7SD84 (CP200) (All versions), SIPROTEC 5 7SD86 (CP200) (All versions), SIPROTEC 5 7SD86 (CP300) (All versions < V9.50), SIPROTEC 5 7SD87 (CP200) (All versions), SIPROTEC 5 7SD87 (CP300) (All versions < V9.50), SIPROTEC 5 7SJ81 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ81 (CP150) (All versions < V9.50), SIPROTEC 5 7SJ82 (CP100) (All versions < V8.89), SIPROTEC 5 7SJ82 (CP150) (All versions < V9.50), SIPROTEC 5 7SJ85 (CP200) (All versions), SIPROTEC 5 7SJ85 (CP300) (All versions < V9.50), SIPROTEC 5 7SJ86 (CP200) (All versions), SIPROTEC 5 7SJ86 (CP300) (All versions < V9.50), SIPROTEC 5 7SK82 (CP100) (All versions < V8.89), SIPROTEC 5 7SK82 (CP150) (All versions < V9.50), SIPROTEC 5 7SK85 (CP200) (All versions), SIPROTEC 5 7SK85 (CP300) (All versions < V9.50), SIPROTEC 5 7SL82 (CP100) (All versions < V8.90), SIPROTEC 5 7SL82 (CP150) (All versions < V9.50), SIPROTEC 5 7SL86 (CP200) (All versions), SIPROTEC 5 7SL86 (CP300) (All versions < V9.50), SIPROTEC 5 7SL87 (CP200) (All versions), SIPROTEC 5 7SL87 (CP300) (All versions < V9.50), SIPROTEC 5 7SS85 (CP200) (All versions), SIPROTEC 5 7SS85 (CP300) (All versions < V9.50), SIPROTEC 5 7ST85 (CP200) (All versions), SIPROTEC 5 7ST85 (CP300) (All versions < V9.64), SIPROTEC 5 7ST86 (CP300) (All versions < V9.64), SIPROTEC 5 7SX82 (CP150) (All versions < V9.50), SIPROTEC 5 7SX85 (CP300) (All versions < V9.50), SIPROTEC 5 7UM85 (CP300) (All versions < V9.50), SIPROTEC 5 7UT82 (CP100) (All versions < V8.90), SIPROTEC 5 7UT82 (CP150) (All versions < V9.50), SIPROTEC 5 7UT85 (CP200) (All versions), SIPROTEC 5 7UT85 (CP300) (All versions < V9.50), SIPROTEC 5 7UT86 (CP200) (All versions), SIPROTEC 5 7UT86 (CP300) (All versions < V9.50), SIPROTEC 5 7UT87 (CP200) (All versions), SIPROTEC 5 7UT87 (CP300) (All versions < V9.50), SIPROTEC 5 7VE85 (CP300) (All versions < V9.50), SIPROTEC 5 7VK87 (CP200) (All versions), SIPROTEC 5 7VK87 (CP300) (All versions < V9.50), SIPROTEC 5 7VU85 (CP300) (All versions < V9.50), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) (All versions installed on CP200 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) (All versions < V9.50 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) (All versions installed on CP200 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) (All versions < V9.50 installed on CP150 and CP300 devices), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) (All versions < V8.89 installed on CP100 devices), SIPROTEC 5 Communication Module ETH-BD-2FO (All versions < V9.50), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V9.50). Affected devices do not properly restrict secure client-initiated renegotiations within the SSL and TLS protocols. This could allow an attacker to create a denial of service condition on the ports 443/tcp and 4443/tcp for the duration of the attack.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Siemens | SIPROTEC 5 6MD84 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 6MD85 (CP200) | — | — |
| Siemens | SIPROTEC 5 6MD85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 6MD86 (CP200) | — | — |
| Siemens | SIPROTEC 5 6MD86 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 6MD89 (CP300) | < V9.64 | V9.64 |
| Siemens | SIPROTEC 5 6MU85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7KE85 (CP200) | — | — |
| Siemens | SIPROTEC 5 7KE85 (CP300) | < V9.64 | V9.64 |
| Siemens | SIPROTEC 5 7SA82 (CP100) | < V8.90 | V8.90 |
| Siemens | SIPROTEC 5 7SA82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SA84 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SA86 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SA86 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SA87 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SA87 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SD82 (CP100) | < V8.90 | V8.90 |
| Siemens | SIPROTEC 5 7SD82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SD84 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SD86 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SD86 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SD87 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SD87 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SJ81 (CP100) | < V8.89 | V8.89 |
| Siemens | SIPROTEC 5 7SJ81 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SJ82 (CP100) | < V8.89 | V8.89 |
| Siemens | SIPROTEC 5 7SJ82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SJ85 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SJ85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SJ86 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SJ86 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SK82 (CP100) | < V8.89 | V8.89 |
| Siemens | SIPROTEC 5 7SK82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SK85 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SK85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SL82 (CP100) | < V8.90 | V8.90 |
| Siemens | SIPROTEC 5 7SL82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SL86 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SL86 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SL87 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SL87 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SS85 (CP200) | — | — |
| Siemens | SIPROTEC 5 7SS85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7ST85 (CP200) | — | — |
| Siemens | SIPROTEC 5 7ST85 (CP300) | < V9.64 | V9.64 |
| Siemens | SIPROTEC 5 7ST86 (CP300) | < V9.64 | V9.64 |
| Siemens | SIPROTEC 5 7SX82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7SX85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7UM85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7UT82 (CP100) | < V8.90 | V8.90 |
| Siemens | SIPROTEC 5 7UT82 (CP150) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7UT85 (CP200) | — | — |
| Siemens | SIPROTEC 5 7UT85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7UT86 (CP200) | — | — |
| Siemens | SIPROTEC 5 7UT86 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7UT87 (CP200) | — | — |
| Siemens | SIPROTEC 5 7UT87 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7VE85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7VK87 (CP200) | — | — |
| Siemens | SIPROTEC 5 7VK87 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 7VU85 (CP300) | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1) | < V9.50, < V8.89 | V9.50 |
| Siemens | SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1) | < V9.50, < V8.89 | V9.50 |
| Siemens | SIPROTEC 5 Communication Module ETH-BD-2FO | < V9.50 | V9.50 |
| Siemens | SIPROTEC 5 Compact 7SX800 (CP050) | < V9.50 | V9.50 |
Advisories 3
- ICSA-22-349-11 Siemens SIPROTEC 5 Devices CISA ICS & IT advisories · Nov 11, 2025
- SSA-552874 SSA-552874: Denial of Service Vulnerability in SIPROTEC 5 Devices Siemens ProductCERT · Nov 11, 2025
- WID-SEC-2022-2294 Siemens SIPROTEC: Mehrere Schwachstellen ermöglichen Denial of Service BSI CERT-Bund (WID) · Dec 12, 2022