Description

In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.

Affected products

VendorProductAffectedFixed
CODESYS CODESYS Control for BeagleBone SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for emPC-A/iMX6 SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for IOT2000 SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for Linux SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for PFC100 SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for PFC200 SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for PLCnext SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for Raspberry Pi SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control for WAGO Touch Panels 600 SL < V4.10.0.0 V4.10.0.0
CODESYS CODESYS Control RTE (for Beckhoff CX) SL < V3.5.19.20 V3.5.19.20
CODESYS CODESYS Control RTE (SL) < V3.5.19.20 V3.5.19.20
CODESYS CODESYS Control Runtime System Toolkit < V3.5.19.20 V3.5.19.20
CODESYS CODESYS Control Win (SL) < V3.5.19.20 V3.5.19.20
CODESYS CODESYS Development System V3 < V3.5.19.20 V3.5.19.20
CODESYS CODESYS HMI (SL) < V3.5.19.20 V3.5.19.20
CODESYS CODESYS Safety SIL2 Runtime Toolkit < V3.5.19.20 V3.5.19.20

Advisories 8

References