A low privileged user can set the date of the devices to the 19th of January 2038 an therefore exceed the 32-Bit time limit. This causes some functions to work unexpected or stop working at all. Both during runtime and after a restart.

Affected products

VendorProductAffectedFixed
WAGO CC100 0751-9x01 < 04.07.01 04.07.01
WAGO PFC100 G1 0750-810x/xxxx-xxxx < 3.10.11, < 03.10.11 3.10.11
WAGO PFC100 G2 0750-811x-xxxx-xxxx < 04.07.01 04.07.01
WAGO PFC200 G1 750-820x-xxx-xxx < 3.10.11, < 03.10.11 3.10.11
WAGO PFC200 G2 750-821x-xxx-xxx < 04.07.01 04.07.01
WAGO TP600 0762-420x/8000-000x < 04.07.01 04.07.01
WAGO TP600 0762-430x/8000-000x < 04.07.01 04.07.01
WAGO TP600 0762-520x/8000-000x < 04.07.01 04.07.01
WAGO TP600 0762-530x/8000-000x < 04.07.01 04.07.01
WAGO TP600 0762-620x/8000-000x < 04.07.01 04.07.01
WAGO TP600 0762-630x/8000-000x < 04.07.01 04.07.01
WAGO WAGO CC100 0751-9x01 < 04.07.01 04.07.01
WAGO WAGO Edge Controller 0752-8303/8000-0002 < 04.07.01 04.07.01