Critical · 9.3 CVE-2025-7693 EUVD-2025-25134GHSA-3p2j-q62h-27w3

Rockwell Automation Micro800 Vulnerability

Published Aug 18, 2025 · Updated Aug 18, 2025 · Assigned by Rockwell

Description

A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.

Affected products

VendorProductAffectedFixed
Rockwell Automation PLC - Micro850 L50E V20.011 - V22.011 —