Description
RTU500 contains a denial-of-service vulnerability in its IEC 61850 MMS server implementation. A malicious user with access to the IEC 61850 interface can trigger improper handling of asynchronous control operations involving special response and timing criteria. This may result in access to invalid memory structures, leading to a software exception, loss of IEC 61850 communications, or device reboot.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Hitachi Energy | RTU500 series CMU firmware | 13.5.1 – ≤ 13.5.4, 13.6.1 – ≤ 13.6.3, 13.7.1 – ≤ 13.7.8, 13.8.1 | — |
Advisories 1