Skip to content
OpenAdvisories
Medium · 5.9 CVE-2026-17539 EUVD-2026-70318GHSA-9w2f-4f52-qcj4

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference…

Published Sep 3, 2026 · Updated Sep 3, 2026 · Assigned by Hitachi Energy

Description

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.

Affected products

VendorProductAffectedFixed
Hitachi Energy RTU500 series CMU firmware 12.7.1 – ≤ 12.7.7, 13.5.1 – ≤ 13.5.4, 13.6.1 – ≤ 13.6.3, 13.7.1 – ≤ 13.7.8, 13.8.1 – ≤ 13.8.2 —

Advisories 2

References