Honeywell IQ4x BMS Controller Missing authentication for critical function

Published Mar 12, 2026 · Updated Mar 30, 2026 · Assigned by icscert

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Affected products

VendorProductAffectedFixed
Honeywell IQ4E v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —
Honeywell IQ412 v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —
Honeywell IQ422 v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —
Honeywell IQ4NC v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —
Honeywell IQ41x v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —
Honeywell IQ3 v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —
Honeywell IQECO v3.50_3.44 – ≤ 4.36 (build 4.3.7.9) —

Public exploits

Exploit or proof-of-concept code for this vulnerability is publicly available, which lowers the bar for attackers. Treat it as a reason to patch sooner.

Third-party code, not reviewed by us. Public PoCs are sometimes fake or contain malware. Read the code first and run it only in an isolated lab, against systems you are authorised to test.

GitHub 1 repository

  • spinfosecurity/BAS-Guardian ★ 1 · Aug 3, 2026

    Free BACnet/BMS vulnerability scanner for building automation systems. Detects CVE-2026-3611 (CVSS 10.0), CVE-2026-24060, and exposed HVAC/BAS controllers via PowerShell or Bash.

Sources: PoC-in-GitHub, Metasploit Framework, Exploit-DB — updated daily. Only links are listed; no exploit code is hosted here.