Description
ANDRITZ HIPASE-250 (formerly 250 SCALA), in the default configuration
of affected versions, exposes its data and configuration endpoint
without any authentication and permissive CORS on every response. An
unauthenticated attacker with network access can read live process
values and server configuration.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| ANDRITZ | HIPASE-250 | ≤ 7.20 | 7.40 |
| ANDRITZ | 250 SCALA | ≤ 7.20 | 7.40 |
Advisories 1
- ICSA-26-225-05 ANDRITZ HIPASE-250 and 250 SCALA CISA ICS & IT advisories · Aug 13, 2026