Summary
Successful exploitation of these vulnerabilities could allow an unauthenticated attacker to obtain access to files and credentials, escalate privileges, and remotely execute arbitrary code.
Vulnerabilities 13
-
Critical 9.8
CVE-2023-1133
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow…
-
Critical 9.8
CVE-2023-1136
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an unauthenticated attacker could generate a valid token, which would lead to authentication bypass.
-
Critical 9.8
CVE-2023-1140
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability that could allow an attacker to achieve unauthenticated remote code execution in the context of an administrator.
-
High 8.8
CVE-2023-1139
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-gateway service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
-
High 8.8
CVE-2023-1141
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a command injection vulnerability that could allow an attacker to inject arbitrary commands, which could result in remote code execution.
-
High 8.8
CVE-2023-1143
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use Lua scripts, which could allow an attacker to remotely execute arbitrary code.
-
High 8.8
CVE-2023-1144
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contains an improper access control vulnerability in which an attacker can use the Device-Gateway service and bypass authorization, which could result in privilege escalation.
-
High 7.8
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could set incorrect directory permis…
-
High 7.8
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targ…
-
High 7.5
CVE-2023-1138
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain an improper access control vulnerability, which could allow an attacker to retrieve Gateway configuration files to obtain plaintext credentials.
-
High 7.5
CVE-2023-1142
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use URL decoding to retrieve system files, credentials, and bypass authentication resulting in privilege escalation.
-
High 7.1
CVE-2023-1134
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a path traversal vulnerability, which could allow an attacker to read local files, disclose plaintext credentials, and escalate privileges.
-
Medium 6.5
CVE-2023-1137
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which a low-level user could extract files and plaintext credentials of administrator users, resulting in privilege escalation.
Revision history
-
#1
CSAF Creation Date
References
-
ICS Advisory ICSA-23-080-02 Web Version
https://www.cisa.gov/news-events/ics-advisories/icsa-23-080-02
-
Recommended Practices
https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01
-
Recommended Practices
https://us-cert.cisa.gov/ics/Recommended-Practices
-
Recommended Practices
https://cisa.gov/ics
-
Recommended Practices
https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf
-
Recommended Practices
https://www.cisa.gov/uscert/ncas/tips/ST04-014