Summary
Successful exploitation of these vulnerabilities could crash the device being accessed.
Vulnerabilities 2
-
Medium 6.5
MZ Automation lib60870 Out-of-bounds Read
A crafted IEC 60870-5-104 I-frame with TypeID 104 (C_TS_NA_1) and an inflated object count causes TestCommand_getFromBuffer to read one byte past the end of the heap-allocated message buffer.
-
Medium 6.5
MZ Automation lib60870 Out-of-bounds Read
A crafted IEC 60870-5-104 I-frame with a declared object count exceeding what fits in the ASDU body causes InformationObject_ParseObjectAddress to read one byte past the end of the heap-allocated message buffer.
Revision history
-
#1
Initial Publication
References
-
ICSA Advisory ICSA-26-211-11 - Web Version
https://www.cisa.gov/news-events/ics-advisories/icsa-26-211-11
-
Recommended Practices
https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01
-
Recommended Practices
https://www.cisa.gov/resources-tools/resources/ics-recommended-practices
-
Recommended Practices
https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf
-
Recommended Practices
https://www.cisa.gov/topics/industrial-control-systems
-
Recommended Practices
https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01
-
Recommended Practices
https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf
-
Recommended Practices
https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b
-
Recommended Practices
https://www.cisa.gov/secure-our-world/teach-employees-avoid-phishing
-
Recommended Practices
https://www.cisa.gov/news-events/news/avoiding-social-engineering-and-phishing-attacks