Skip to content
OpenAdvisories
Medium · 6.5 CVE-2026-61893 EUVD-2026-51362GHSA-gfjj-vr9m-mw6f

MZ Automation lib60870 Out-of-bounds Read

Published Jul 30, 2026 · Updated Jul 31, 2026 · Assigned by icscert

Description

A crafted IEC 60870-5-104 I-frame with TypeID 104 (C_TS_NA_1) and an
inflated object count causes TestCommand_getFromBuffer to read one byte
past the end of the heap-allocated message buffer.

Affected products

VendorProductAffectedFixed
MZ Automation lib60870 2.4.0 2.4.1

Fixed in Linux distributions

Distributions backport fixes, so the version that fixes this vulnerability differs per release — upgrade to at least the version shown. From the distributions' security trackers and advisories.

ReleasePackageFixed inAdvisory
Ubuntu 26.10 lib60870 No fix yet —
Ubuntu 26.04 LTS lib60870 No fix yet —

Advisories 1

References