Summary
Hitachi Energy is publishing this cybersecurity advisory in response to the security findings reported by Dragos affecting end-of-life RTU500 CMU firmware version 9.x. The reported findings are associated with legacy RTU500 firmware versions that were developed according to the cybersecurity requirements, threat landscape, and industry practices that existed at the time of their release. As cybersecurity threats and security expectations have evolved, these end-of-life versions no longer incorporate many of the security controls and hardening measures that are standard in modern industrial control systems. Over successive RTU500 releases, Hitachi Energy has continuously enhanced the security of the product through the introduction of additional security features, protocol hardening, stronger authentication and access controls, encrypted communications, and other security-by-design improvements. While the findings reported by Dragos do not affect currently supported RTU500 CMU firmware versions, there is a likelihood that the end-of-life versions 11.x and prior are affected by these vulnerabilities. Since the end-of-life versions are no longer maintained with security updates, Hitachi Energy strongly recommends upgrading to a currently supported RTU500 firmware version. Customers should also implement appropriate defense-in-depth measures and cybersecurity best practices to reduce risk and strengthen the security posture of their operational environments. Please refer to the Recommended Immediate Actions for information about the mitigation/remediation.
Vulnerabilities 6
-
Critical 10.0
Phoenix Contact Software ProConOs and MultiProg Missing Authentication for Critical Function
Phoenix Contact ProConOs and MultiProg do not require authentication, which allows remote attackers to execute arbitrary commands via protocol-compliant traffic.
-
Critical 9.8CVE-2010-2965 EPSS 58%
The WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on the Rockwell Automation 1756…
-
Critical 9.1CVE-2026-8065 Public exploit
An authentication bypass vulnerability in the firmware update endpoint of Hitachi Energy RTU500 end-of-life versions al…
-
Critical 9.1
A directory traversal vulnerability in the file upload functionality of Hitachi Energy RTU500 end-of-life versions allo…
-
High 7.5
Phoenix Contact: Classic line industrial controllers prone to inadequate integrity check of PLC
Download of Code Without Integrity Check vulnerability in PHOENIX CONTACT classic line PLCs allows an unauthenticated remote attacker to modify some or all applications on a PLC.
-
Medium 6.5
An improper authorization vulnerability in the end-of-life versions of RTU500’s web application allows an authenticated…
Revision history
-
#2
Initial CISA Republication of Hitachi Energy PSIRT 8DBD000251 advisory
-
#1
Initial public release
References
-
[1] Hitachi Energy Notification for Industrial Control Systems Cybersecurity Best Practices
https://publisher.hitachienergy.com/preview?DocumentID=8DBD000235&LanguageCode=en&DocumentPartId=&Action=Launch
-
Vulnerabilities in Hitachi Energy RTU500 End-of-Life versions
https://publisher.hitachienergy.com/preview?DocumentID=8DBD000251&LanguageCode=en&DocumentPartId=&Action=launch
-
ICS Advisory ICSA-26-279-06 - Web Version
https://www.cisa.gov/news-events/ics-advisories/icsa-26-279-06
-
Recommended Practices
https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01
-
Recommended Practices
https://www.cisa.gov/resources-tools/resources/ics-recommended-practices
-
Recommended Practices
https://www.cisa.gov/topics/industrial-control-systems
-
Recommended Practices
https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf
-
Recommended Practices
https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf
-
Recommended Practices
https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b