Summary
Promass 83 devices utilizing 499ES EtherNet/IP (ENIP) Stack by Real Time Automation (RTA) are vulnerable to a stack-based buffer overflow.
Update A, 2021-10-07:
added credits
changed title from "ENDRESS+HAUSER: Promass 83 with Ether/IP affected by DoS vulnerability" to "ENDRESS+HAUSER: Promass 83 with EtherNet/IP affected by a stack-based buffer overflow"
Details
Impact
The vulnerability described can lead to a denial of service or even remote code execution.
Mitigation
If an immediate firmware update is not possible, the only way to prevent an attack is to disable communication via EtherNet/IP.
Remediation
Endress+Hauser provides updated firmware versions (Firmware versions >1.00.00) for the related product from the Proline portfolio which fixes the vulnerability. Endress+Hauser strongly recommends customers to update to the new fixed version. For support, please contact your local service center.
Vulnerabilities 1
-
Unscored —
Real Time Automation EtherNet/IP
499ES EtherNet/IP (ENIP) Adaptor Source Code is vulnerable to a stack-based buffer overflow, which may allow an attacker to send a specially crafted packet that may result in a denial-of-service condition or code execution.
Revision history
-
#3
Fix: firmware category, added distribution
-
#2
Update A
-
#1
Initial revision.
References
-
Endress+Hauser advisory overview at CERT@VDE
https://certvde.com/de/advisories/vendor/endress+hauser/
-
VDE-2021-040: Endress+Hauser: Promass 83 with EtherNet/IP affected by a stack-based buffer overflow - HTML
https://certvde.com/en/advisories/VDE-2021-040