Skip to content
OpenAdvisories

Summary

Several WAGO firmwares installed on different devices are impacted by various CODESYS vulnerabilities. These affect the runtime, visualization, and OPC UA server.

Details

Impact
CVE-2025-0694:
The used OPC UA protocol supports an outdated RSA encryption scheme. This allows an unauthenticated attacker to compromise the private key of the OPC UA server and bypass authentication or decrypt transmitted data.

CVE-2025-1468:
On a device with an executed Visualization an unauthenticated attacker can access static visualization files like texts or images via the web browser.

CVE-2025-2595:
Through the SysFile component (included by the CODESYS Control runtime system) an authenticated user is able to access the local file system. An authenticated attacker could use this to set a whitelist that gives access to paths inside or outside the default directory. This is possible by using placeholder similar to environmental variables.

Remediation
Update to Firmware version 04.08.01 (FW30), 03.10.11 (FW22 Patch 2) or 01.05.01. For the latest Custom Firmware please contact the WAGO support.

Vulnerabilities 3

Revision history

  1. #1

    Release version.

References