Skip to content
OpenAdvisories
High VDE-2026-003 16 CVEs

Endress+Hauser: Multiple products prone to multiple vulnerabilities in e!Runtime and CODESYS V3 Runtime

Published Mar 31, 2026 · Updated Apr 1, 2026 · Revision 2

Summary

Multiple Endress+Hauser devices are prone to vulnerabilities found in e!Runtime and the CODESYS V3 framework.

Details

Impact
An external attacker could exploit the vulnerabilities to cause denial-of-service, overwrite memory, or execute arbitrary code.

Mitigation
The CDC 90 device is not designed for network connectivity by default. Since it is not connected to a network, the vulnerabilities cannot be exploited. However, if the customer chooses to connect the device to a network, the default firewall settings should be maintained, as this will mitigate the security vulnerabilities.

For the CC 100 and PFC 200 devices, ensure that the default firewall settings remain intact and that both PLC Runtime and PLC WebVisu are disabled. This configuration effectively mitigates the identified security vulnerabilities.

Remediation
Although the CDC 90 device is typically not connected to a network, making exploitation of the vulnerabilities unlikely, Endress+Hauser has provided an update to eliminate the vulnerabilities should the device be connected.

For the CC 100 and PFC 200 devices, Endress+Hauser provides updated firmware that incorporates WAGO's security fixes for the identified vulnerabilities. Customers are advised to update to the latest version

For support, please contact your local service center.

| Product | Fixed Version |
|--------|--------------|
| CC 100 (751-9301) | FW 28 |
| PFC 200 (750-82xx/xxx-xxx) | FW 28 |
| CDC 90 | V3.5.19.0 |

Vulnerabilities 16

Revision history

  1. #1.0.1

    Edited a typo in product tree.

  2. #1.0.0

    Initial version

References