High 7.5
GE UR family exposure of sensitive information to an unauthorized actor
GE UR firmware versions prior to version 8.1x web server interface is supported on UR over HTTP protocol. It allows sensitive information exposure without authentication.
-
Critical 9.8
GE UR family insecure default variable initialization
GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user.
-
Medium 5.3
GE UR family exposure of sensitive information to an unauthorized actor
GE UR firmware versions prior to version 8.1x shares MODBUS memory map as part of the communications guide. GE was made aware a “Last-key pressed” MODBUS register can be used to gain unauthorized information.
-
Critical 9.8
GE UR family Unrestricted Upload of File with Dangerous Type
GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate use…
-
Medium 5.3
GE UR family input validation
GE UR firmware versions prior to version 8.1x web server task does not properly handle receipt of unsupported HTTP verbs, resulting in the web server becoming temporarily unresponsive after receiving a series of unsupported HTTP requests. When unresponsive, t…
-
Medium 5.3
GE UR family input validation
GE UR firmware versions prior to version 8.1x supports web interface with read-only access. The device fails to properly validate user input, making it possible to perform cross-site scripting attacks, which may be used to send a malicious script. Also, UR Fi…