Vendor
Rockwell Automation
317 known vulnerabilities.
Products
317 results · Feed
-
Medium 6.7
Rockwell Automation ISaGRAF5 Runtime Uncontrolled Search Path Element
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGR…
-
High 7.5
Rockwell Automation ISaGRAF5 Runtime Cleartext Transmission of Sensitive Information
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol un…
-
Medium 5.5
Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker cou…
-
High 7.1
IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611
A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitr…
-
High 7.8
The DeskLock tool provided with FactoryTalk View SE uses a weak encryption algorithm that may allow a local, authentica…
-
Medium 6.1
The web interface of the 1734-AENTR communication module is vulnerable to stored XSS. A remote, unauthenticated attacke…
-
Medium 5.3
The web interface of the 1734-AENTR communication module mishandles authentication for HTTP POST requests. A remote, un…
-
High 7.3
Rockwell Automation FactoryTalk View SE
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enab…
-
Medium 4.3
Rockwell Automation FactoryTalk View SE
All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built …
-
High 7.5
Rockwell Automation FactoryTalk View SE
In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends a…
-
Critical 9.0
Rockwell Automation FactoryTalk View SE
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell …
-
Unscored —
A maliciously crafted program file opened by an unsuspecting user of Rockwell Automation Arena Simulation Software vers…
-
Unscored —
A maliciously crafted program file opened by an unsuspecting user of Rockwell Automation Arena Simulation Software vers…
-
Unscored —
Rockwell Automation CompactLogix 5370 Uncontrolled Resource Consumption
An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Con…
-
Unscored —
Rockwell Automation CompactLogix 5370 Stack-based Buffer Overflow
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact…
-
Medium 6.1
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 110…
-
Unscored —CVE-2019-6553 EPSS 66%
A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue i…
-
Unscored —
Rockwell Automation EtherNet/IP Web Server Modules 1756-EWEB (includes 1756-EWEBK) Version 5.001 and earlier, and Compa…
-
Unscored —
Rockwell PLC5/SLC5/0x/RSLogix Credentials management
The potential exists for exposure of the product's password used to restrict unauthorized access to Rockwell PLC5/SLC5/0x/RSLogix 1785-Lx and 1747-L5x controllers. The potential exists for an unauthorized programming and configuration client to gain access to…
-
Unscored —
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5…
-
Unscored —
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5…
-
Unscored —
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5…
-
Unscored —
In Rockwell Automation FactoryTalk Services Platform 2.90 and earlier, a remote unauthenticated attacker could send num…
-
Unscored —
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote, unauthenticated t…
-
Unscored —CVE-2018-14829 EPSS 16%
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. This vulnerability may allow a remote threat actor to in…
-
Unscored —
Rockwell Automation RSLinx Classic Versions 4.00.01 and prior. A remote, unauthenticated threat actor may intentionally…
-
Unscored —
Without quotation marks, any whitespace in the file path for Rockwell Automation FactoryTalk Activation version 4.00.02…
-
High 7.1
Rockwell Automation Micrologix 1400 Improper Input Validation
The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed pack…
-
Medium 6.3
Rockwell RSLogix 5000 Insufficiently Protected Credentials
Rockwell Automation RSLogix 5000 7 through 20.01, and 21.0, does not properly implement password protection for .ACD files (aka project files), which allows local users to obtain sensitive information or modify data via unspecified vectors.
-
Medium 5.0CVE-2012-6441 EPSS 57%
Rockwell Automation ControlLogix PLC Information Exposure
An information exposure of confidential information results when the device receives a specially crafted CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP. Successful exploitation of this vulnerability could cause loss of confident…
-
High 7.5CVE-2012-6438 EPSS 36%
Rockwell Automation ControlLogix PLC Improper Input Validation
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the NIC to crash. Successful ex…
-
High 8.5CVE-2012-6439 EPSS 23%
Rockwell Automation ControlLogix PLC Improper Access Control
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that changes the product’s configuration and network parameters, a DoS condition can occur. This…
-
High 7.5CVE-2012-6435 EPSS 43%
Rockwell Automation ControlLogix PLC Improper Access Control
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the CPU to stop logic execution and enter a fault state, a DoS can occur. This si…
-
Critical 9.8CVE-2012-6437 EPSS 11%
Rockwell Automation ControlLogix PLC Improper Authentication
The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitation of this vulnerability could cause los…
-
High 7.5CVE-2012-6442 EPSS 35%
Rockwell Automation ControlLogix PLC Improper Access Control
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the product to reset, a DoS can occur. This situation could cause loss of availab…
-
High 7.5CVE-2012-6436 EPSS 35%
Rockwell Automation ControlLogix PLC Improper Input Validation
The device does not properly validate the data being sent to the buffer. An attacker can send a malformed CIP packet to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP, which creates a buffer overflow and causes the CPU to crash. Successful ex…
-
Medium 4.8
Rockwell Automation ControlLogix PLC Improper Input Validation
The Web server password authentication mechanism used by the products is vulnerable to a MitM and Replay attack. Successful exploitation of this vulnerability will allow unauthorized access of the product’s Web server to view and alter product configuration a…