Description

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINAMICS PERFECT HARMONY GH180 Drives (Drives manufactured before 2021-08-13), SINUMERIK MC (All versions < V6.15), SINUMERIK ONE (All versions < V6.15). Affected devices are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks.

Affected products

VendorProductAffectedFixed
Siemens SIMATIC Drive Controller family All versions < V2.9.2 —
Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) All versions —
Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) All versions < V21.9 —
Siemens SIMATIC S7-1200 CPU family (incl. SIPLUS variants) All versions < V4.5.0 —
Siemens SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) All versions < V2.9.2 —
Siemens SIMATIC S7-1500 Software Controller All versions < V21.9 —
Siemens SIMATIC S7-PLCSIM Advanced All versions < V4.0 —
Siemens SINAMICS PERFECT HARMONY GH180 Drives Drives manufactured before 2021-08-13 —
Siemens SINUMERIK MC All versions < V6.15 —
Siemens SINUMERIK ONE All versions < V6.15 —

Advisories 8

References