Critical · 9.8 CVE-2023-28489 EUVD-2023-32159GHSA-x9qv-5m74-x74p

A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05)…

Published Apr 11, 2023 · Updated Feb 13, 2025 · Assigned by siemens

Description

A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default.
The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.

Affected products

VendorProductAffectedFixed
Siemens CP-8031 MASTER MODULE All versions < CPCI85 V05 —
Siemens CP-8050 MASTER MODULE All versions < CPCI85 V05 —