Description
A stack-based buffer overflow in an unauthenticated CGI handler of the
Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially
crafted HTTP/S POST requests, leading to memory corruption, webserver restart
and hypothetically potential arbitrary code execution with webserver privileges.
Authentication is not required to exploit this vulnerability.
Affected products
| Vendor | Product | Affected | Fixed |
|---|---|---|---|
| Danfoss | AK-SM8xxA | ≤ 5.4.0 | — |
Public exploits
Exploit or proof-of-concept code for this vulnerability is publicly available, which lowers the bar for attackers. Treat it as a reason to patch sooner.
GitHub 1 repository
-
cveForge/CVE-2026-129713 ★ 0 · Nov 24, 2026
Danfoss AK-SM SCADA Web Interface Stack Buffer Overflow — CVSS 9.8
Sources: PoC-in-GitHub, Metasploit Framework, Exploit-DB — updated daily. Only links are listed; no exploit code is hosted here.
Advisories 1
- ICSA-26-328-03 Danfoss AK-SM 8xxA Series CISA ICS & IT advisories · Nov 24, 2026